OUTPUT |
Output Volt Amp Capacity (VA) | 1500 | Output kVA Capacity (kVA) | 1.5 | Output Watt Capacity (Watts) | 900 | Power Factor | 0.6 | Nominal Output Voltage(s) Supported | 220V; 230V; 240V | Nominal Voltage Details | 230V default (voltage selection via back panel switches) | Frequency Compatibility | 50 / 60 Hz | Output Voltage Regulation (Line Mode) | -9% / + 5% | Output Voltage Regulation (Battery Mode) | +/- 5% | Output Receptacles | (8) C13 | Included Output Power Cables | Includes 2 C13 to C14 output power cables | Output AC Waveform (AC Mode) | Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 4.1A (220V),3.9A (230V), 3.8 (240V) | Nominal Input Voltage(s) Supported | 220V AC; 230V AC; 240V AC | UPS Input Connection Type | C14 inlet | UPS Input Connection Description | IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 8 min. (900w) | Half Load Runtime (min.) | 20 min. (450w) | DC System Voltage (VDC) | 36 | Battery Recharge Rate (Included Batteries) | Less than 8 hours from 10% to 90% (typical, full load discharge) | Internal UPS Replacement Battery Cartridge | RBC36-SLT | Battery Access | Provides the battery access door | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | No |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 182 to 278 (230v), 190 to 290 (240v), 174 to 266 (220v) | Overvoltage Correction | Voltage reduction of 12% applies when input is 244 to 278 (230v), 254 to 290 (240v), 232 to 266 (220v) | Undervoltage Correction | Voltage boost of 14% applies when input is 182 to 206 (230v), 190 to 216 (240v), 174 to 198 (220) |
|
USER INTERFACE, ALERTS & CONTROLS |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection | Alarm Cancel Operation | Power-fail alarm can be silenced using alarm-cancel switch | Audible Alarm | Audible alarm indicates power failure and overload conditions | LED Indicators | 9 LEDs indicate line power, battery power, AVR, overload and replace battery status – with a 3-LED level meter for load and battery charge level |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating | 350 | UPS AC Suppression Response Time | Instantaneous | UPS Dataline Suppression | 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Primary Form Factor | Tower | UPS Power Module Dimensions (hwd, cm) | 26 x 17.1 x 33.7 | UPS Power Module Weight (kg) | 20.4 | UPS Shipping Dimensions (hwd / cm) | 35.6 x 24.8 x 47 | Shipping Weight (kg) | 22.1 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 195.3 | Battery Mode BTU / Hr. (Full Load) | 582.9 | AC Mode Efficiency Rating (100% Load) | 94% | Audible Noise | Audible Noise < 50 dBA at Front Side 1 Meter |
|
COMMUNICATIONS |
Communications Interface | USB; DB9 Serial; Slot for SNMP/Web interface | Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions | PowerAlert Software | Included | Communications Cable | USB and DB9 cabling included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | 4-8 milliseconds | Low Voltage Transfer to Battery Power (Setpoint) | 174V (220V), 182V (230V) or 190V (240V) | High Voltage Transfer to Battery Power (Setpoint) | 266V (220V), 278V (230V) or 290V (240V) |
|
SPECIAL FEATURES |
Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Hot swappable batteries |
|
CERTIFICATIONS |
UPS Certifications | CE; Tested to GOST (Russia); Tested to SASO (Saudi Arabia); Meets FCC Part 15 Category A (EMI) | UPS Certification Details | CE / IEC 62040 |
|
WARRANTY |
Product Warranty Period (International) | 2-year limited warranty | Product Warranty Period (Mexico) | 2-year limited warranty | Product Warranty Period (Puerto Rico) | 2-year limited warranty |
|