OUTPUT
|
| Output Volt Amp Capacity (VA) |
1500 |
| Output kVA Capacity (kVA) |
1.5 |
| Output Watt Capacity (Watts) |
1350 |
| Output kW Capacity (kW) |
1.35 |
| Output Capacity Details |
Output derates to 1200 watts in all external battery configurations |
| Power Factor |
0.9 |
| Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
| Nominal Voltage Details |
230v nominal inverter output voltage |
| Frequency Compatibility |
50 / 60 Hz |
| Output Voltage Regulation (Line Mode) |
+6% / -15% |
| Output Voltage Regulation (Battery Mode) |
+/- 5% |
| Output Receptacles |
(8) C13 |
| Included Output Power Cables |
Set of 2 C13 to C14 power cables included |
| Load Management Receptacles |
Two switchable two-outlet C13 load banks |
| Output AC Waveform (AC Mode) |
Sine wave |
| Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
| Rated input current (Maximum Load) |
6.9A |
| Nominal Input Voltage(s) Supported |
230V AC |
| UPS Input Connection Type |
C14 inlet |
| UPS Input Connection Description |
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
| Input Circuit Breakers |
10A |
| Input Phase |
Single-Phase |
|
BATTERY
|
| Full Load Runtime (min.) |
4.9 min. (1350w) |
| Half Load Runtime (min.) |
13.6 min. (675w) |
| Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
| External Battery Pack Compatibility |
BP36V15-2U(limit 1); BP36V42-3U(multi-pack compatible); BP36V27-2US(multi-pack compatible) |
| DC System Voltage (VDC) |
36 |
| Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% (typical, full load discharge) |
| Internal UPS Replacement Battery Cartridge |
RBC93-2U |
| Battery Access |
Front panel battery access door |
| Battery Replacement Description |
Hot-swappable, user replaceable batteries |
| Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
| Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278 |
| Overvoltage Correction |
Input voltages between 244 and 278 are reduced by 12% |
| Undervoltage Correction |
Input voltages between 182 and 206 are boosted by 12% |
| Severe Undervoltage Correction |
Input voltages between 158 and 182 are boosted by 24% |
|
USER INTERFACE, ALERTS & CONTROLS
|
| Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
| Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
| Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
| Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
|
SURGE / NOISE SUPPRESSION
|
| UPS AC Suppression Joule Rating |
350 |
| UPS AC Suppression Response Time |
Instantaneous |
| EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
| Included Mounting Accessory Description |
4 post rackmount installation accessories included |
| Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND); 2-4 post front rail rackmount(UPSHDEARKIT) |
| Primary Form Factor |
Rackmount |
| UPS Power Module Dimensions (hwd, cm) |
8.9 x 44.4 x 34.3 |
| Rack Height (U Spaces) |
2 |
| UPS Power Module Weight (kg) |
19.6 |
| UPS Shipping Dimensions (hwd / cm) |
22.9 x 61 x 52.1 |
| Shipping Weight (kg) |
30.2 |
| Cooling Method |
Fan |
| UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
| Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| Relative Humidity |
0 to 95%, non-condensing |
| AC Mode BTU / Hr. (Full Load) |
139 |
| AC Mode Efficiency Rating (100% Load) |
97% |
|
COMMUNICATIONS
|
| Communications Interface |
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
| Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
| PowerAlert Software |
Included |
| Communications Cable |
USB and DB9 cabling included |
| WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
| Transfer Time |
6 ms. (AC to DC) / 1 ms. (DC to AC) |
| Low Voltage Transfer to Battery Power (Setpoint) |
158 |
| High Voltage Transfer to Battery Power (Setpoint) |
278 |
|
SPECIAL FEATURES
|
| Grounding Lug |
Back panel grounding lug |
| Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
| High Availability UPS Features |
Hot swappable batteries |
| Green Energy-Saving Features |
Greater than 95% efficiency – GREEN UPS; Individually controllable load banks |
|
CERTIFICATIONS
|
| UPS Certifications |
CE; Tested to GOST (Russia) |
| UPS Certification Details |
EN62040-1, 62040-2 (Class A) |
|
WARRANTY
|
| Product Warranty Period (Worldwide) |
2-year limited warranty |
|