OUTPUT |
Output Volt Amp Capacity (VA) | 2200 | Output kVA Capacity (kVA) | 2.2 | Output Watt Capacity (Watts) | 1920 | Output kW Capacity (kW) | 1.92 | Nominal Output Voltage(s) Supported | 220V; 230V; 240V | Nominal Voltage Details | 230V inverter output in battery mode | Frequency Compatibility | 50 / 60 Hz | Output Voltage Regulation (Line Mode) | -15%, +6% | Output Voltage Regulation (Battery Mode) | +/- 5% | Output Receptacles | (8) C13 | Included Output Power Cables | Includes 3 C13 to C14 output power cables | Load Management Receptacles | Two switchable single-outlet C13 load banks | Hot-Swap PDU options | PDUBHV20 (2U / 6 C13, 2 C19 outlets) | Output AC Waveform (AC Mode) | Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 10.7A | Nominal Input Voltage(s) Supported | 230V AC | UPS Input Connection Type | C20 inlet | UPS Input Connection Description | IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles | Input Circuit Breakers | 15A | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 5 min. (1920w) | Half Load Runtime (min.) | 11.9 min. (960w) | Expandable Battery Runtime | Extended runtime supported via optional external battery packs | External Battery Pack Compatibility | BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) | DC System Voltage (VDC) | 48 | Battery Recharge Rate (Included Batteries) | Less than 4.5 hours from 10% to 90% (typical, full load discharge) | Internal UPS Replacement Battery Cartridge | RBC94-2U | Battery Access | Front panel battery access door | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | Yes |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278 | Overvoltage Correction | Voltage reduction of 12% applies when input is between 244-278V | Undervoltage Correction | Voltage boost of 12% applies when input voltage is between 183-206V | Severe Undervoltage Correction | Voltage boost of 24% applies when input voltage is between 158-182V |
|
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display | Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) | Switches | 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions | Alarm Cancel Operation | Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available | Audible Alarm | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating | 350 | UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Included Mounting Accessory Description | 4 post rackmount installation accessories included | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 8.9 x 44.4 x 49.5 | Rack Height (U Spaces) | 2 | UPS Power Module Weight (kg) | 31.2 | UPS Shipping Dimensions (hwd / cm) | 23.5 x 62.9 x 57.2 | Shipping Weight (kg) | 37.3 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 161 | AC Mode Efficiency Rating (100% Load) | 98% |
|
COMMUNICATIONS |
Communications Interface | USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface | Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions | PowerAlert Software | Included | Communications Cable | USB, DB9 and EPO cabling included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | 6 ms. (AC to DC) / 1 ms. (DC to AC) | Low Voltage Transfer to Battery Power (Setpoint) | 158V | High Voltage Transfer to Battery Power (Setpoint) | 278V |
|
SPECIAL FEATURES |
Grounding Lug | Back panel grounding lug | Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Hot swappable batteries | Green Energy-Saving Features | Greater than 95% efficiency – GREEN UPS; Individually controllable load banks |
|
CERTIFICATIONS |
UPS Certifications | CE | UPS Certification Details | IEC 62040-1, IEC 62040-2 Class A EMI, GOST |
|
WARRANTY |
Product Warranty Period (International) | 2-year limited warranty | Product Warranty Period (Mexico) | 2-year limited warranty | Product Warranty Period (Puerto Rico) | 2-year limited warranty |
|