OUTPUT
|
Output Volt Amp Capacity (VA) |
3000 |
Output kVA Capacity (kVA) |
3 |
Output Watt Capacity (Watts) |
2700 |
Output kW Capacity (kW) |
2.7 |
Power Factor |
.9 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230v nominal inverter output voltage |
Frequency Compatibility |
50 / 60 Hz |
Output Voltage Regulation (Line Mode) |
+6%, -15% |
Output Voltage Regulation (Battery Mode) |
+/-5% |
Output Receptacles |
(8) C13; (1) C19 |
Included Output Power Cables |
Set of 3 C13 to C14 power cables included |
Load Management Receptacles |
Two switchable single outlet C13 load banks |
Output AC Waveform (AC Mode) |
Pure Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
14.1A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
C20 inlet |
UPS Input Connection Description |
IEC320-C20 input connection accepts a variety of user supplied detachable C19 output cordsets to match country or site specific power sources |
Input Circuit Breakers |
20A |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
3.9 min. (2700w) |
Half Load Runtime (min.) |
11.1 min. (1350w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 5 hours from 10 to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC58-2U |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, replaceable batteries |
Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278 |
Overvoltage Correction |
Input voltages between 244 and 278 are reduced by 12% |
Undervoltage Correction |
Input voltages between 206 and 183 are boosted by 12% |
Severe Undervoltage Correction |
Input voltages between 158 and 183 are boosted by 24% |
|
USER INTERFACE, ALERTS & CONTROLS
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
350 |
EMI / RFI AC Noise Suppression |
Yes |
AC Suppression Response Time |
Instantaneous |
|
PHYSICAL
|
Included Mounting Accessory Description |
4 post rackmount installation hardware included |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
8.9 x 44.4 x 49.5 |
Rack Height (U Spaces) |
2 |
UPS Power Module Weight (kg) |
28.5 |
UPS Shipping Dimensions (hwd / cm) |
22.9 x 60.3 x 52.1 |
Shipping Weight (kg) |
33 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
158 |
AC Mode Efficiency Rating (100% Load) |
98% |
|
COMMUNICATIONS
|
Communications Interface |
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
Included |
Communications Cable |
USB, DB9 and EPO cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
6 milliseconds (AC to battery mode), 1 millisecond (Battery to AC mode) |
Low Voltage Transfer to Battery Power (Setpoint) |
158 |
High Voltage Transfer to Battery Power (Setpoint) |
278 |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Green Energy-Saving Features |
Greater than 95% efficiency – GREEN UPS; Individually controllable load banks; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS
|
UPS Certifications |
CE; ROHS (Restriction of Hazardous Substances) |
UPS Certification Details |
IEC 62040-1, IEC 62040-2 Class A EMI, GOST |
|
WARRANTY
|
Product Warranty Period (Worldwide) |
2-year limited warranty |
|