OUTPUT |
Output Volt Amp Capacity (VA) | 5000 | Output kVA Capacity (kVA) | 5 | Output Watt Capacity (Watts) | 3750 | Output kW Capacity (kW) | 3.75 | Power Factor | 0.75 | Nominal Output Voltage(s) Supported | 220V; 230V; 240V | Nominal Voltage Details | 230v nominal inverter output voltage | Frequency Compatibility | 50 / 60 Hz | Output Voltage Regulation (Line Mode) | -17%, +8% | Output Voltage Regulation (Battery Mode) | +/- 5% | Output Receptacles | (8) C13; (3) C19 | Included Output Power Cables | Includes 3 C13 to C14 output power cables | Output Circuit Breakers | 15A (x3) breaker supports 1 C19 outlet each, 10A (x2) breaker supports 4 C13 outlets each | Output AC Waveform (AC Mode) | Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 27A | Nominal Input Voltage(s) Supported | 230V AC | UPS Input Connection Type | Hardwire | UPS Input Connection Description | Hardwire input supports International 230V input (L, N, PE) | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 8.5 min. (3750w) | Half Load Runtime (min.) | 20 min. (1875w) | Expandable Battery Runtime | Extended runtime supported via optional external battery packs | External Battery Pack Compatibility | BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) | DC System Voltage (VDC) | 48 | Battery Recharge Rate (Included Batteries) | Less than 4 hours from 10% to 90% (typical, full load discharge) | Internal UPS Replacement Battery Cartridge | RBC94-3U(quantity 3) | Battery Access | Front panel battery access door | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | Yes |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 170 to 282 | Overvoltage Correction | Input voltages between 245 and 282 are reduced by 12% | Undervoltage Correction | Input voltages between 170 and 199 are boosted by 12% |
|
USER INTERFACE, ALERTS & CONTROLS |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation | Alarm Cancel Operation | Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status | Audible Alarm | Audible alarm indicates power-failure, overload and low-battery conditions | LED Indicators | 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating | 480 | UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITHD); Tower(2-9USTAND) | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 13.3 x 44.4 x 63.5 | Rack Height (U Spaces) | 3 | Maximum Device Depth (cm) | 63.5 | UPS Power Module Weight (kg) | 64.9 | UPS Shipping Dimensions (hwd / cm) | 28.6 x 58.4 x 80 | Shipping Weight (kg) | 82.6 | Cooling Method | Fans | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 271 | AC Mode Efficiency Rating (100% Load) | 98% |
|
COMMUNICATIONS |
Communications Interface | USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface | Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions | PowerAlert Software | Included | Communications Cable | USB and DB9 cabling included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | 7 ms (AC to Battery); 1 ms (Battery to AC) typical | Low Voltage Transfer to Battery Power (Setpoint) | 170 | High Voltage Transfer to Battery Power (Setpoint) | 282 |
|
SPECIAL FEATURES |
Grounding Lug | Back panel grounding lug | Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Hot swappable batteries | Green Energy-Saving Features | Greater than 95% efficiency – GREEN UPS |
|
CERTIFICATIONS |
UPS Certifications | CE | UPS Certification Details | Class A (EMI) |
|
WARRANTY |
Product Warranty Period (International) | 2-year limited warranty | Product Warranty Period (Mexico) | 2-year limited warranty | Product Warranty Period (Puerto Rico) | 2-year limited warranty |
|