OUTPUT
|
Output Volt Amp Capacity (VA) |
5000 |
Output kVA Capacity (kVA) |
5 |
Output Watt Capacity (Watts) |
3750 |
Output kW Capacity (kW) |
3.75 |
Power Factor |
0.75 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230v nominal inverter output voltage |
Frequency Compatibility |
50 / 60 Hz |
Output Voltage Regulation (Line Mode) |
-17%, +8% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(8) C13; (3) C19 |
Included Output Power Cables |
Includes 3 C13 to C14 output power cables |
Output Circuit Breakers |
15A (x3) breaker supports 1 C19 outlet each, 10A (x2) breaker supports 4 C13 outlets each |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
27A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
Hardwire |
UPS Input Connection Description |
Hardwire input supports International 230V input (L, N, PE) |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
8.5 min. (3750w) |
Half Load Runtime (min.) |
20 min. (1875w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 4 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC94-3U(quantity 3) |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 170 to 282 |
Overvoltage Correction |
Input voltages between 245 and 282 are reduced by 12% |
Undervoltage Correction |
Input voltages between 170 and 199 are boosted by 12% |
|
USER INTERFACE, ALERTS & CONTROLS
|
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status |
Audible Alarm |
Audible alarm indicates power-failure, overload and low-battery conditions |
LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
480 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Installation Form Factors Supported with Included Accessories |
4 post 19 inch rackmount |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITHD); Tower(2-9USTAND) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
13.3 x 44.4 x 63.5 |
Rack Height (U Spaces) |
3 |
Maximum Device Depth (cm) |
63.5 |
UPS Power Module Weight (kg) |
64.9 |
UPS Shipping Dimensions (hwd / cm) |
28.6 x 58.4 x 80 |
Shipping Weight (kg) |
82.6 |
Cooling Method |
Fans |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
271 |
AC Mode Efficiency Rating (100% Load) |
98% |
|
COMMUNICATIONS
|
Communications Interface |
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
Included |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
7 ms (AC to Battery); 1 ms (Battery to AC) typical |
Low Voltage Transfer to Battery Power (Setpoint) |
170 |
High Voltage Transfer to Battery Power (Setpoint) |
282 |
|
SPECIAL FEATURES
|
Grounding Lug |
Back panel grounding lug |
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Green Energy-Saving Features |
Greater than 95% efficiency – GREEN UPS |
|
CERTIFICATIONS
|
UPS Certifications |
CE |
UPS Certification Details |
Class A (EMI) |
|
WARRANTY
|
Product Warranty Period (International) |
2-year limited warranty |
Product Warranty Period (Mexico) |
2-year limited warranty |
Product Warranty Period (Puerto Rico) |
2-year limited warranty |
|