OUTPUT
|
|
INPUT
|
Rated input current (Maximum Load) |
31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V) |
Nominal Input Voltage(s) Supported |
200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
Nominal Input Voltage Description |
Factory configured to 208V |
UPS Input Connection Type |
Hardwire |
UPS Input Connection Description |
Supports North American 208/240V input (L1,L2,G) or International 230/220/240V (L,N,PE) input wiring; Optional SU30ACORD offers NEMA L6-30P input |
Recommended Electrical Service |
40A (200/208v); 30-32A (220/230/240v) |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
2 minutes (5400 watts) |
Half Load Runtime (min.) |
8.5 minutes (2700 watts) |
Expandable Battery Runtime |
Runtime is expandable with external battery packs |
External Battery Pack Compatibility |
BP192V1037C-1PH; BP192V12-3U; BP192V1407C-1PH; BP192V557C-1PH; BP192V787C-1PH |
DC System Voltage (VDC) |
192 |
Battery Recharge Rate (Included Batteries) |
6 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC5-192 |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable internal batteries |
Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Online, double-conversion power conditioning |
Overvoltage Correction |
Corrects overvoltages as high as 300V (<90% load) and 280V (full load) |
Undervoltage Correction |
Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly |
|
USER INTERFACE, ALERTS & CONTROLS
|
Front Panel LCD Display |
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats |
Switches |
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads. |
Alarm Cancel Operation |
Alarm cancel switch |
Audible Alarm |
Unique audible alarms for all major UPS, environmental and power conditions (see manual) |
LED Indicators |
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Response Time |
Instantaneous |
|
PHYSICAL
|
Included Mounting Accessory Description |
Includes 4 post rackmount installation accessories |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
17.4 x 44.5 x 52.6 |
Rack Height (U Spaces) |
4 |
Maximum Device Depth (cm) |
52.6 |
UPS Power Module Weight (kg) |
49 |
UPS Shipping Dimensions (hwd / cm) |
32.3 x 59.9 x 73.9 |
Shipping Weight (kg) |
71.1 |
Cooling Method |
Fans |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
1767 |
AC Economy Mode BTU / Hr. (Full Load) |
707 |
AC Mode Efficiency Rating (100% Load) |
90% |
AC Economy Mode Efficiency Rating (100% Load) |
96% |
Audible Noise |
60 dBA at front side 1 meter |
Operating Elevation (m) |
0-3000 m |
|
COMMUNICATIONS
|
Communications Interface |
USB |
Network Monitoring Port Description |
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports |
PowerAlert Software |
Included |
Communications Cable |
USB, DB9 serial and EPO cables included |
WatchDog Compatibility |
Yes |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
No transfer time (0 ms.) in online, double-conversion mode |
Transfer Time (Economy Mode) |
8 ms. typical power failure response in optional economy mode |
Low Voltage Transfer to Battery Power (Setpoint) |
156V (full load) / 100V (50% load or less, derates linearly) |
High Voltage Transfer to Battery Power (Setpoint) |
280V (full load) / 300V (90% load or less) |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
|
CERTIFICATIONS
|
UPS Certifications |
CE; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to UL1778 (USA) |
UPS Certification Details |
IEC 61000-4-5 1995 B Surge Immunity |
|
WARRANTY
|
Product Warranty Period (Worldwide) |
2-year limited warranty |
Connected Equipment Insurance (U.S., Canada & Puerto Rico) |
$250,000 Ultimate Lifetime Insurance |
|