OUTPUT |
Output Volt Amp Capacity (VA) | 8000 | Output kVA Capacity (kVA) | 8 | Output Watt Capacity (Watts) | 7200 | Output kW Capacity (kW) | 7.2 | Output Capacity Details | Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less | Power Factor | 0.9 | Crest Factor | 3:1 | Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V | Nominal Voltage Details | Voltage selection via front panel LCD interface | Frequency Compatibility | 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion | Frequency Compatibility Details | Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating) | Output Voltage Regulation (Line Mode) | +/- 2% | Output Voltage Regulation (Economy Line Mode) | +/- 10% | Output Voltage Regulation (Battery Mode) | +/- 2% | Output Receptacles | (6) C19 | Output Circuit Breakers | 20A double-pole (x6) protects 1 C19 outlet each | Output AC Waveform (AC Mode) | Pure Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V) | Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 230V AC; 240V AC | UPS Input Connection Type | Hardwire | UPS Input Connection Description | Supports North American 208/240V input (L1,L2,G) and International 230/220/240V (L,N,PE) input wiring | Recommended Electrical Service | 50A | Voltage Compatibility (VAC) | 200; 208; 230; 240 | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 5.5 min. (7200w) | Half Load Runtime (min.) | 13.5 min. (3600w) | Expandable Battery Runtime | Supports extended runtime with optional external battery packs | External Battery Pack Compatibility | BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH | DC System Voltage (VDC) | 240 | Battery Recharge Rate (Included Batteries) | Less than 6 hours from 10% to 90% (typical, full load discharge) | Battery Replacement Description | Hot-swappable, user replaceable external battery packs | Expandable Runtime | Yes |
|
VOLTAGE REGULATION |
Voltage Regulation Description | 2% output voltage regulation in standard online, double-conversion mode | Overvoltage Correction | Corrects overvoltages up to 300V | Undervoltage Correction | Corrects undervoltages as low as 100V |
|
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display | Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual) | Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement | Alarm Cancel Operation | Alarm cancel switch | Audible Alarm | Unique audible alarms for all major UPS, environmental and power conditions (see manual) | LED Indicators | 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Included Mounting Accessory Description | 2 sets of adjustable 4 post rack rails included (for separate UPS and battery pack components); 2-9USTAND tower kit included (supports up to 9U in tower format) | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITHD) | Optional Mounting Accessory Notes | 2 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate power module and battery pack | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 13.1 x 44.4 x 65.6 | Rack Height (U Spaces) | 6 | Maximum Device Depth (cm) | 82.6 | UPS Power Module Weight (kg) | 19.5 | UPS Dimensions Details | Installed Whole System Maximum Rack Depth refers to the installed depth with the included Bypass PDU attached to the UPS power module | Included Battery Pack Dimensions (hwd / cm) | 13.3 x 44.4 x 63.5 | Included Battery Pack Weight (kg) | 72 | UPS Shipping Dimensions (hwd / cm) | 101 x 80 x 58.4 | Shipping Weight (kg) | 150.3 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 2732 | AC Economy Mode BTU / Hr. (Full Load) | 1020 | AC Mode Efficiency Rating (100% Load) | 91% | AC Economy Mode Efficiency Rating (100% Load) | 96% | Audible Noise | 60 dBA at front side 1 meter | Operating Elevation (m) | 0-3000 m |
|
COMMUNICATIONS |
Communications Interface | USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface | Network Monitoring Port Description | Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports | PowerAlert Software | Included | Communications Cable | USB, DB9 serial and EPO cables included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | No transfer time (0 ms.) in online, double-conversion mode | Transfer Time (Economy Mode) | 8 ms. typical power failure response in optional economy mode | Low Voltage Transfer to Battery Power (Setpoint) | 100V | High Voltage Transfer to Battery Power (Setpoint) | 300V |
|
SPECIAL FEATURES |
Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | Economy Mode Operation | Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of +/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1 millisecond transfer time between modes. | High Availability UPS Features | Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Manual bypass switch | Green Energy-Saving Features | High efficiency economy mode operation; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS |
UPS Certifications | Assured and Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); CE; Meets FCC Part 15 Category A (EMI) | UPS Certification Details | IEC 61000-4-5 1995 B Surge Immunity |
|
WARRANTY |
Product Warranty Period (Worldwide) | 2-year limited warranty | Connected Equipment Insurance (U.S., Canada & Puerto Rico) | $250,000 Ultimate Lifetime Insurance |
|