OUTPUT
|
| Output Volt Amp Capacity (VA) |
8000 |
| Output kVA Capacity (kVA) |
8 |
| Output Watt Capacity (Watts) |
7200 |
| Output kW Capacity (kW) |
7.2 |
| Output Capacity Details |
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less |
| Power Factor |
0.9 |
| Crest Factor |
3:1 |
| Nominal Output Voltage(s) Supported |
200V; 208V; 220V; 230V; 240V |
| Nominal Voltage Details |
Voltage selection via front panel LCD interface |
| Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
| Frequency Compatibility Details |
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating) |
| Output Voltage Regulation (Line Mode) |
+/- 2% |
| Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
| Output Voltage Regulation (Battery Mode) |
+/- 2% |
| Output Receptacles |
(6) C19 |
| Output Circuit Breakers |
20A double-pole (x6) protects 1 C19 outlet each |
| Output AC Waveform (AC Mode) |
Pure Sine wave |
| Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
| Rated input current (Maximum Load) |
46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V) |
| Nominal Input Voltage(s) Supported |
200V AC; 208V AC; 230V AC; 240V AC |
| UPS Input Connection Type |
Hardwire |
| UPS Input Connection Description |
Supports North American 208/240V input (L1,L2,G) and International 230/220/240V (L,N,PE) input wiring |
| Recommended Electrical Service |
50A |
| Voltage Compatibility (VAC) |
200; 208; 230; 240 |
| Input Phase |
Single-Phase |
|
BATTERY
|
| Full Load Runtime (min.) |
5.5 min. (7200w) |
| Half Load Runtime (min.) |
13.5 min. (3600w) |
| Expandable Battery Runtime |
Supports extended runtime with optional external battery packs |
| External Battery Pack Compatibility |
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH |
| DC System Voltage (VDC) |
240 |
| Battery Recharge Rate (Included Batteries) |
Less than 6 hours from 10% to 90% (typical, full load discharge) |
| Battery Replacement Description |
Hot-swappable, user replaceable external battery packs |
| Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
| Voltage Regulation Description |
2% output voltage regulation in standard online, double-conversion mode |
| Overvoltage Correction |
Corrects overvoltages up to 300V |
| Undervoltage Correction |
Corrects undervoltages as low as 100V |
|
USER INTERFACE, ALERTS & CONTROLS
|
| Front Panel LCD Display |
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual) |
| Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement |
| Alarm Cancel Operation |
Alarm cancel switch |
| Audible Alarm |
Unique audible alarms for all major UPS, environmental and power conditions (see manual) |
| LED Indicators |
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
|
SURGE / NOISE SUPPRESSION
|
| UPS AC Suppression Response Time |
Instantaneous |
| EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
| Included Mounting Accessory Description |
2 sets of adjustable 4 post rack rails included (for separate UPS and battery pack components); 2-9USTAND tower kit included (supports up to 9U in tower format) |
| Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITHD) |
| Optional Mounting Accessory Notes |
2 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate power module and battery pack |
| Primary Form Factor |
Rackmount |
| UPS Power Module Dimensions (hwd, cm) |
13.1 x 44.4 x 65.6 |
| Rack Height (U Spaces) |
6 |
| Maximum Device Depth (cm) |
82.6 |
| UPS Power Module Weight (kg) |
19.5 |
| UPS Dimensions Details |
Installed Whole System Maximum Rack Depth refers to the installed depth with the included Bypass PDU attached to the UPS power module |
| Included Battery Pack Dimensions (hwd / cm) |
13.3 x 44.4 x 63.5 |
| Included Battery Pack Weight (kg) |
72 |
| UPS Shipping Dimensions (hwd / cm) |
101 x 80 x 58.4 |
| Shipping Weight (kg) |
150.3 |
| Cooling Method |
Fan |
| UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
| Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| Relative Humidity |
0 to 95%, non-condensing |
| AC Mode BTU / Hr. (Full Load) |
2732 |
| AC Economy Mode BTU / Hr. (Full Load) |
1020 |
| AC Mode Efficiency Rating (100% Load) |
91% |
| AC Economy Mode Efficiency Rating (100% Load) |
96% |
| Audible Noise |
60 dBA at front side 1 meter |
| Operating Elevation (m) |
0-3000 m |
|
COMMUNICATIONS
|
| Communications Interface |
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
| Network Monitoring Port Description |
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports |
| PowerAlert Software |
Included |
| Communications Cable |
USB, DB9 serial and EPO cables included |
| WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
| Transfer Time |
No transfer time (0 ms.) in online, double-conversion mode |
| Transfer Time (Economy Mode) |
8 ms. typical power failure response in optional economy mode |
| Low Voltage Transfer to Battery Power (Setpoint) |
100V |
| High Voltage Transfer to Battery Power (Setpoint) |
300V |
|
SPECIAL FEATURES
|
| Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
| Economy Mode Operation |
Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of +/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1 millisecond transfer time between modes. |
| High Availability UPS Features |
Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Manual bypass switch |
| Green Energy-Saving Features |
High efficiency economy mode operation; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS
|
| UPS Certifications |
Assured and Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); CE; Meets FCC Part 15 Category A (EMI) |
| UPS Certification Details |
IEC 61000-4-5 1995 B Surge Immunity |
|
WARRANTY
|
| Product Warranty Period (Worldwide) |
2-year limited warranty |
| Connected Equipment Insurance (U.S., Canada & Puerto Rico) |
$250,000 Ultimate Lifetime Insurance |
|