OUTPUT
|
Output Volt Amp Capacity (VA) |
1000 |
Output kVA Capacity (kVA) |
1 |
Output Watt Capacity (Watts) |
800 |
Output Capacity Details |
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits) |
Power Factor |
0.8 |
Crest Factor |
3:1 |
Nominal Output Voltage(s) Supported |
200V; 220V; 230V; 240V |
Nominal Voltage Details |
230V default |
Frequency Compatibility |
50 / 60 Hz |
Frequency Compatibility Details |
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start |
Output Voltage Regulation (Line Mode) |
+/- 2% |
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
Output Voltage Regulation (Battery Mode) |
+/- 2% |
Output Receptacles |
(6) C13 |
Included Output Power Cables |
Includes 2 C13 to C14 power cables |
Hot-Swap PDU options |
PDUBHV10 (2U / 8 C13 outlets) |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
5.1A (200V), 4.9A (208V), 4.6A (220V), 4.4A (230V), 4.2A (240V) |
Nominal Input Voltage(s) Supported |
200V AC; 220V AC; 230V AC; 240V AC |
UPS Input Connection Type |
C14 inlet |
UPS Input Connection Description |
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
Input Circuit Breakers |
8A |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
4 min. (800w) |
Half Load Runtime (min.) |
12 min. (400w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP24V15RT2U(limit 1); BP24V28-2U(limit 1); BP24V70-3U(multi-pack compatible); BP24V36-2US(multi-pack compatible) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 6 hours from 10% to 80% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC92-2U |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Online, double-conversion power conditioning |
Overvoltage Correction |
2% output voltage regulation during overvoltages to 275 |
Undervoltage Correction |
2% output voltage regulation during undervoltages to 156 |
Severe Undervoltage Correction |
2% output voltage regulation during undervoltages to 130 (under 70% load only) |
|
USER INTERFACE, ALERTS & CONTROLS
|
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
LED Indicators |
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
1225 |
UPS AC Suppression Response Time |
Instantaneous |
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Included Mounting Accessory Description |
4 post rackmount installation accessories included |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
8.9 x 44.4 x 34.3 |
Rack Height (U Spaces) |
2 |
UPS Power Module Weight (kg) |
12.7 |
UPS Shipping Dimensions (hwd / cm) |
22.2 x 60.3 x 51.4 |
Shipping Weight (kg) |
18.9 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
406.4 |
AC Economy Mode BTU / Hr. (Full Load) |
173.6 |
Battery Mode BTU / Hr. (Full Load) |
442.8 |
AC Mode Efficiency Rating (100% Load) |
87% |
AC Economy Mode Efficiency Rating (100% Load) |
94% |
|
COMMUNICATIONS
|
Communications Interface |
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications |
PowerAlert Software |
Included |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
No transfer time (0 ms.) in online, double-conversion mode |
Low Voltage Transfer to Battery Power (Setpoint) |
160V (100% load), 130V ( <70% load) |
High Voltage Transfer to Battery Power (Setpoint) |
275 |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Automatic inverter bypass; Hot swappable batteries |
Green Energy-Saving Features |
High efficiency economy mode operation; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS
|
UPS Certifications |
CE; Tested to SASO (Saudi Arabia) |
UPS Certification Details |
Kuwait |
|
WARRANTY
|
Product Warranty Period (Worldwide) |
2-year limited warranty |
|