OUTPUT |
Output Volt Amp Capacity (VA) | 2200 | Output kVA Capacity (kVA) | 2.2 | Output Watt Capacity (Watts) | 1600 | Output kW Capacity (kW) | 1.6 | Output Capacity Details | OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) . Also it is possible when bypass input voltage or frequency are OUTSIDE bypass limits in SHUTDOWN . | Power Factor | 0.7 | Crest Factor | 3:1 | Nominal Output Voltage(s) Supported | 200V; 220V; 230V; 240V | Nominal Voltage Details | 230V default | Frequency Compatibility | 50 / 60 Hz | Frequency Compatibility Details | Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start | Output Voltage Regulation (Line Mode) | +/- 3% | Output Voltage Regulation (Economy Line Mode) | +/- 10% | Output Voltage Regulation (Battery Mode) | +/- 3% | Output Receptacles | (4) C13; (2) C19 | Included Output Power Cables | Includes 2 C13 to C14 and 1 C20 to C19 output power cables | Load Management Receptacles | Two switchable single-outlet C19 load banks | Hot-Swap PDU options | PDUBHV20 (2U / 6 C13, 2 C19 outlets) | Output AC Waveform (AC Mode) | Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 9.7A (200V), 9.3A (208V), 8.8A (220V), 8.5A (230V), 8.1A (240V) | Nominal Input Voltage(s) Supported | 200V AC; 220V AC; 230V AC; 240V AC | UPS Input Connection Type | C20 inlet | UPS Input Connection Description | C20 inlet accepts user-supplied AC power cord | Input Circuit Breakers | 15A | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 5 min. (1600w) | Half Load Runtime (min.) | 14 min. (800w) | Expandable Battery Runtime | Supports extended runtime with optional external battery packs | External Battery Pack Compatibility | BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) | DC System Voltage (VDC) | 48 | Battery Recharge Rate (Included Batteries) | Less than 6 hours from 10% to 80% (typical, full load discharge) | Internal UPS Replacement Battery Cartridge | RBC94-2U | Battery Access | Front panel battery access door | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | Yes |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Online, double-conversion power conditioning | Overvoltage Correction | 3% output voltage regulation during overvoltages to 275 | Undervoltage Correction | 3% output voltage regulation during undervoltages to 156 | Severe Undervoltage Correction | 3% output voltage regulation during undervoltages to 130 (under 70% load only) |
|
USER INTERFACE, ALERTS & CONTROLS |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation | Alarm Cancel Operation | Power-fail alarm can be silenced using alarm-cancel switch | Audible Alarm | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions | LED Indicators | 14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information. Also gives the 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating | 660 | UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Included Mounting Accessory Description | 4 post rackmount installation accessories included | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 8.9 x 44.4 x 48.3 | Rack Height (U Spaces) | 2 | UPS Power Module Weight (kg) | 21.6 | UPS Shipping Dimensions (hwd / cm) | 23 x 51.4 x 58.4 | Shipping Weight (kg) | 27.1 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 885.6 | AC Economy Mode BTU / Hr. (Full Load) | 347.2 | Battery Mode BTU / Hr. (Full Load) | 885.6 | AC Mode Efficiency Rating (100% Load) | 86% | AC Economy Mode Efficiency Rating (100% Load) | 94% | Audible Noise | Audible Noise: 50dBA At Front Side 1 Meter |
|
COMMUNICATIONS |
Communications Interface | USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface | Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications | PowerAlert Software | Included | Communications Cable | USB and DB9 cabling included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | No transfer time (0 ms.) in online, double-conversion mode | Low Voltage Transfer to Battery Power (Setpoint) | 160V (100% load), 130V ( <70% load) | High Voltage Transfer to Battery Power (Setpoint) | 275 |
|
SPECIAL FEATURES |
Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Automatic inverter bypass; Hot swappable batteries | Green Energy-Saving Features | High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS |
UPS Certifications | CE; Tested to SASO (Saudi Arabia) | UPS Certification Details | Kuwait |
|
WARRANTY |
Product Warranty Period (Worldwide) | 2-year limited warranty |
|