OUTPUT
|
Output Volt Amp Capacity (VA) |
3000 |
Output kVA Capacity (kVA) |
3 |
Output Watt Capacity (Watts) |
2100 |
Output kW Capacity (kW) |
2.1 |
Power Factor |
0.7 |
Crest Factor |
3:1 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230V default |
Frequency Compatibility |
50 / 60 Hz |
Frequency Compatibility Details |
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start |
Output Voltage Regulation (Line Mode) |
+/- 2% |
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
Output Voltage Regulation (Battery Mode) |
+/- 2% |
Output Receptacles |
(8) C13 |
Included Output Power Cables |
Includes 3 C13 to C14 output power cables |
Hot-Swap PDU options |
PDUBHV20 (2U / 6 C13, 2 C19 outlets) |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
13.6A (220V), 13A (230V), 12.5A (240V) |
Nominal Input Voltage(s) Supported |
220V AC; 230V AC; 240V AC |
UPS Input Connection Type |
C20 inlet |
UPS Input Connection Description |
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
Input Circuit Breakers |
20A |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
5 min. (2100w) |
Half Load Runtime (min.) |
14 min. (1050w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP72V15-2U(limit 1); BP72V28RT-3U(multi-pack compatible) |
DC System Voltage (VDC) |
72 |
Battery Recharge Rate (Included Batteries) |
Less than 6 hours from 10% to 90% |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Online, double-conversion power conditioning |
Overvoltage Correction |
2% output voltage regulation during overvoltages to 280 |
Undervoltage Correction |
2% output voltage regulation during undervoltages to 175 |
Severe Undervoltage Correction |
2% output voltage regulation during undervoltages to 80 (under 50% load only) |
|
USER INTERFACE, ALERTS & CONTROLS
|
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
LED Indicators |
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
570 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Primary Form Factor |
Tower |
UPS Power Module Dimensions (hwd, cm) |
37.3 x 14 x 42.4 |
UPS Power Module Weight (kg) |
30.5 |
UPS Shipping Dimensions (hwd / cm) |
49.3 x 24.9 x 60.5 |
Shipping Weight (kg) |
33.5 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
793.3 |
AC Economy Mode BTU / Hr. (Full Load) |
455.7 |
Battery Mode BTU / Hr. (Full Load) |
973.6 |
AC Mode Efficiency Rating (100% Load) |
90% |
AC Economy Mode Efficiency Rating (100% Load) |
94% |
Audible Noise |
< 45 dB at front side 1m |
|
COMMUNICATIONS
|
Communications Interface |
DB9 Serial; Contact closure; Slot for SNMP/Web interface |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications |
PowerAlert Software |
Included |
Communications Cable |
DB9 cabling included |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
No transfer time (0 ms.) in online, double-conversion mode |
Low Voltage Transfer to Battery Power (Setpoint) |
175V (100% load), 80V ( <50% load) |
High Voltage Transfer to Battery Power (Setpoint) |
280 |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Automatic inverter bypass |
|
CERTIFICATIONS
|
UPS Certifications |
CE |
UPS Certification Details |
CE EN62040-1-1, EN62040-2 Class A |
|
WARRANTY
|
Product Warranty Period (Worldwide) |
2-year limited warranty |
|