OUTPUT |
Output Volt Amp Capacity (VA) | 1000 | Output kVA Capacity (kVA) | 1 | Output Watt Capacity (Watts) | 900 | Output kW Capacity (kW) | 0.9 | Power Factor | 0.9 | Nominal Output Voltage(s) Supported | 220V; 230V; 240V | Nominal Voltage Details | 230v nominal inverter output voltage | Frequency Compatibility | 50 / 60 Hz | Output Voltage Regulation (Line Mode) | +6%, -11% | Output Voltage Regulation (Battery Mode) | +/- 5% | Output Receptacles | (6) C13 | Included Output Power Cables | Includes 2 C13 to C14 output power cables | Load Management Receptacles | Two switchable two-outlet C13 load banks | Hot-Swap PDU options | PDUBHV10 (2U / 8 C13 outlets) | Output AC Waveform (AC Mode) | Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 4.8A | Nominal Input Voltage(s) Supported | 230V AC | UPS Input Connection Type | C14 inlet | UPS Input Connection Description | IEC320-C14 input connection accepts a variety of user supplied detachable C13 output cordsets to match country or site-specific power sources | Input Circuit Breakers | 10A | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 3.6 min. (900w) | Half Load Runtime (min.) | 11.9 min (450w) | DC System Voltage (VDC) | 24 | Battery Recharge Rate (Included Batteries) | Less than 4.5 hours from 10% to 90% (typical, full load discharge) | Internal UPS Replacement Battery Cartridge | See Tripp Lite RBC selector guide | Battery Access | Front panel battery access door | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | No |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 182 to 278 | Overvoltage Correction | Input voltages between 244 and 278 are reduced by 12% | Undervoltage Correction | Input voltages between 182 and 206 are boosted by 12% |
|
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display | Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) | Switches | 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions | Alarm Cancel Operation | Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available | Audible Alarm | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions | LED Indicators | 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating | 350 | UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Included Mounting Accessory Description | 4 post rackmount installation accessories included | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND); 2-4 post front rail rackmount(UPSHDEARKIT) | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 8.9 x 44.4 x 34.3 | Rack Height (U Spaces) | 2 | UPS Power Module Weight (kg) | 15.4 | UPS Shipping Dimensions (hwd / cm) | 22.9 x 61 x 51.4 | Shipping Weight (kg) | 16.3 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 100 | AC Mode Efficiency Rating (100% Load) | 97% |
|
COMMUNICATIONS |
Communications Interface | DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) | Network Monitoring Port Description | Supports detailed monitoring of UPS and site power conditions | PowerAlert Software | Included | Communications Cable | USB and DB9 cabling included | WatchDog Compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER |
Transfer Time | 2-4 milliseconds | Low Voltage Transfer to Battery Power (Setpoint) | 182 | High Voltage Transfer to Battery Power (Setpoint) | 278 |
|
SPECIAL FEATURES |
Grounding Lug | Back panel grounding lug | Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Hot swappable batteries | Green Energy-Saving Features | Greater than 95% efficiency – GREEN UPS; Individually controllable load banks |
|
CERTIFICATIONS |
UPS Certifications | CE; ROHS (Restriction of Hazardous Substances); Tested to GOST (Russia) | UPS Certification Details | IEC 62040-1, IEC 62040-2 Class A EMI |
|
WARRANTY |
Product Warranty Period (International) | 2-year limited warranty | Product Warranty Period (Mexico) | 2-year limited warranty | Product Warranty Period (Puerto Rico) | 2-year limited warranty |
|