OUTPUT
|
Output Volt Amp Capacity (VA) |
750 |
Output Watt Capacity (Watts) |
500 |
Power Factor |
0.7 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230V default (voltage selection via back panel switches) |
Frequency Compatibility |
50 / 60 Hz |
Output Voltage Regulation (Line Mode) |
-11%, +6% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(6) C13 |
Included Output Power Cables |
Includes 2 C13 to C14 output power cables |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
Rated input current (Maximum Load) |
3.6A (220V), 3.5A (230V), 3.4A (240V) |
Nominal Input Voltage(s) Supported |
220V AC; 230V AC; 240V AC |
UPS Input Connection Type |
C14 inlet |
UPS Input Connection Description |
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
Input Phase |
Single-Phase |
|
BATTERY
|
Full Load Runtime (min.) |
5 min. (500w) |
Half Load Runtime (min.) |
15 min. (250w) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 4 hours to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC24-SLT |
Battery Access |
Provides the battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
No |
|
VOLTAGE REGULATION
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 290V |
Overvoltage Correction |
Voltage reduction of 12% applies when input is 232-266 (220V), 244-278 (230V), 254-290 (240V) |
Undervoltage Correction |
Voltage boost of 15% applies when input is 175-198 (220V), 182-206 (230V), 190-216 (240V) |
Severe Undervoltage Correction |
Voltage boost of 30% applies when input is 151-174 (220V), 158-181 (230V), 166-190 (240V) |
|
USER INTERFACE, ALERTS & CONTROLS
|
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch |
Audible Alarm |
Audible alarm indicates power failure and overload conditions |
LED Indicators |
9 LEDs indicate line power, battery power, AVR, overload and replace battery status – with a 3-LED level meter for load and battery charge level |
|
SURGE / NOISE SUPPRESSION
|
UPS AC Suppression Joule Rating |
504 |
UPS AC Suppression Response Time |
Instantaneous |
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
EMI / RFI AC Noise Suppression |
Yes |
|
PHYSICAL
|
Primary Form Factor |
Tower |
UPS Power Module Dimensions (hwd, cm) |
26 x 17.1 x 33.7 |
UPS Power Module Weight (kg) |
15.5 |
UPS Shipping Dimensions (hwd / cm) |
35.6 x 24.8 x 47 |
Shipping Weight (kg) |
17.5 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
73 |
Battery Mode BTU / Hr. (Full Load) |
349 |
AC Mode Efficiency Rating (100% Load) |
96% |
Audible Noise |
Audible Noise < 50 dBA at Front Side 1 Meter |
|
COMMUNICATIONS
|
Communications Interface |
USB (HID enabled); DB9 Serial; Slot for SNMP/Web interface |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
Included |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
LINE / BATTERY TRANSFER
|
Transfer Time |
4-8 milliseconds |
Low Voltage Transfer to Battery Power (Setpoint) |
151 (220V), 158 (230V), 166 (240V) |
High Voltage Transfer to Battery Power (Setpoint) |
266V (220V), 278V (230V) or 290V (240V) |
|
SPECIAL FEATURES
|
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Green Energy-Saving Features |
Provides greater than 95% efficiency – GREEN UPS |
|
CERTIFICATIONS
|
UPS Certifications |
CE; Tested to GOST (Russia); Tested to SASO (Saudi Arabia) |
UPS Certification Details |
EN62040-1, EN62040-2 |
|
WARRANTY
|
Product Warranty Period (International) |
2-year limited warranty |
Product Warranty Period (Mexico) |
2-year limited warranty |
Product Warranty Period (Puerto Rico) |
2-year limited warranty |
|