OUTPUT
|
| Output Volt Amp Capacity (VA) |
10000 |
| Output kVA Capacity (kVA) |
10 |
| Output Watt Capacity (Watts) |
7000 |
| Output kW Capacity (kW) |
7 |
| Power Factor |
0.7 |
| Crest Factor |
3:1 |
| Nominal Output Voltage(s) Supported |
200V; 220V; 230V; 240V |
| Nominal Voltage Details |
Voltage selection via front panel LCD interface |
| Frequency Compatibility |
50 / 60 Hz |
| Output Voltage Regulation (Line Mode) |
+/- 2% |
| Output Voltage Regulation (Battery Mode) |
+/- 2% |
| Output Receptacles |
Hardwire |
| Output AC Waveform (AC Mode) |
Sine wave |
| Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
INPUT
|
| Rated input current (Maximum Load) |
50A |
| Nominal Input Voltage(s) Supported |
220/380V (3ph wye); 230/400V (3ph wye); 240/415V (3ph wye) |
| Nominal Input Voltage Description |
Also supports 200/346V input (AC 3 phase wye); 3-Phase Wye, 4 wire (L1, L2, L3, N, G) |
| UPS Input Connection Type |
Hardwire |
| Input Phase |
3-Phase |
|
BATTERY
|
| Full Load Runtime (min.) |
5 min. (7000w) |
| Half Load Runtime (min.) |
14 min. (3500w) |
| Expandable Battery Runtime |
Supports extended runtime with optional external battery packs |
| External Battery Pack Compatibility |
BP240V10RT3U |
| Expandable Runtime Description |
Runtime is expandable using external battery packs |
| DC System Voltage (VDC) |
240 |
| Battery Recharge Rate (Included Batteries) |
5 hours to 80% |
| Battery Replacement Description |
Hot-swappable, replaceable batteries |
| Expandable Runtime |
Yes |
|
VOLTAGE REGULATION
|
| Voltage Regulation Description |
Online, double-conversion power conditioning |
| Overvoltage Correction |
Maintains continuous operation without using battery power during overvoltages to 485 (3-Phase, 4-Wire plus ground, wye), reducing output within 2% of nominal |
| Undervoltage Correction |
Maintains continuous operation without using battery power during undervoltages to 305 (3-Phase, 4-Wire plus ground, wye), increasing output within 2% of nominal |
|
USER INTERFACE, ALERTS & CONTROLS
|
| Front Panel LCD Display |
Selectable LCD screen |
| Switches |
Power, self test, alarm cancel, LCD scroll and select switches |
| Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch |
| Audible Alarm |
Audible alarms for power failure, battery low, bypass and system fault |
| LED Indicators |
Combination LCD / LED screen offers offers complete status information |
|
SURGE / NOISE SUPPRESSION
|
| EMI / RFI AC Noise Suppression |
Yes |
| AC Suppression Joule Rating |
1980 |
| AC Suppression Response Time |
Instantaneous |
|
PHYSICAL
|
| Included Mounting Accessory Description |
4 post rack rails included; tower kit included |
| Primary Form Factor |
Rackmount |
| UPS Power Module Dimensions (hwd, cm) |
13.5 x 43.9 x 68.1 |
| Maximum Device Depth (cm) |
68.1 |
| UPS Power Module Weight (kg) |
28 |
| Included Battery Pack Dimensions (hwd / cm) |
13.5 x 43.9 x 68.1 |
| Included Battery Pack Weight (kg) |
65.1 |
| UPS Shipping Dimensions (hwd / cm) |
118.1 x 56.6 x 84.1 |
| Shipping Weight (kg) |
99.2 |
| Cooling Method |
Fan |
| UPS Housing Material |
Steel |
|
ENVIRONMENTAL
|
| Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| Relative Humidity |
0 to 95%, non-condensing |
| AC Mode BTU / Hr. (Full Load) |
1800 |
| Battery Mode BTU / Hr. (Full Load) |
1800 |
| AC Mode Efficiency Rating (100% Load) |
91% |
| Audible Noise |
< 50dba @ 1m |
|
COMMUNICATIONS
|
| Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
| Network Monitoring Port Description |
SNMP card is pre-installed |
| Communications Cable |
DB9 cabling included |
|
LINE / BATTERY TRANSFER
|
| Transfer Time |
No transfer time (0 ms.) in online, double-conversion mode |
| Low Voltage Transfer to Battery Power (Setpoint) |
305 |
| High Voltage Transfer to Battery Power (Setpoint) |
485 |
|
SPECIAL FEATURES
|
| Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
| High Availability UPS Features |
Automatic inverter bypass; Hot swappable batteries |
| Green Energy-Saving Features |
High efficiency economy mode operation |
|
CERTIFICATIONS
|
| UPS Certifications |
CE |
| UPS Certification Details |
Tested to CE EN62040-2, EN61000-4-5 |
|
WARRANTY
|
| Product Warranty Period (International) |
2-year limited warranty |
| Product Warranty Period (Mexico) |
2-year limited warranty |
| Product Warranty Period (Puerto Rico) |
2-year limited warranty |
|