OUTPUT |
Output Volt Amp Capacity (VA) | 6000 | Output kVA Capacity (kVA) | 6 | Output Watt Capacity (Watts) | 4200 | Output kW Capacity (kW) | 4.2 | Output Capacity Details | Supports up to 102% load continuously in double conversion mode, 102 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 90% or less | Power Factor | 0.7 | Crest Factor | 3:1 | Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V | Nominal Voltage Details | Voltage selection via front panel LCD interface | Frequency Compatibility | 50 / 60 Hz | Frequency Compatibility Details | Output frequency matches input nominal on startup | Output Voltage Regulation (Line Mode) | +/- 2% | Output Voltage Regulation (Economy Line Mode) | +/- 10% | Output Voltage Regulation (Battery Mode) | +/- 2% | Output Receptacles | Hardwire | Output Receptacle Backplate Options | Optional SUPDM11 backplate adds 2 L6-30R outlets and L6-30P input cord | Output Circuit Breakers | 40A double-pole | Output AC Waveform (AC Mode) | Pure Sine wave | Output AC Waveform (Battery Mode) | Pure Sine wave |
|
INPUT |
Rated input current (Maximum Load) | 30A | Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 220V AC; 230V AC; 240V AC | UPS Input Connection Type | Hardwire | UPS Input Connection Description | Supports North American 208/240V input (L1,L2,G) and International 230/220/240V (L,N,PE) input wiring; Optional SUPDM11 backplate adds 2 L6-30R outlets and L6-30P input cord | Input Circuit Breakers | 40A double-pole | Recommended Electrical Service | 30A 208/220/230/240V | Input Phase | Single-Phase |
|
BATTERY |
Full Load Runtime (min.) | 8 min. (4200w) | Half Load Runtime (min.) | 20 min. (2100w) | Expandable Battery Runtime | Includes one non-expandable BP240V7RT3U(limit 1) external battery pack. No additional BP240V7RT3U external battery packs can be connected to the host UPS, beyond the one included with the SU6000RT3UHV UPS bundle. All additional battery packs connected beyond the included BP240V7RT3U, must be BP240V10RT3U, BP240V557C-1PH, BP240V787C-1PH, BP240V1037C-1PH or BP240V1407C-1PH | External Battery Pack Compatibility | BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH | DC System Voltage (VDC) | 240 | Battery Recharge Rate (Included Batteries) | Less than 6 hours from 10% to 80% (typical, full load discharge) | Battery Replacement Description | Hot-swappable, user replaceable batteries | Expandable Runtime | Yes |
|
VOLTAGE REGULATION |
Voltage Regulation Description | Online, double-conversion power conditioning | Overvoltage Correction | 2% output voltage regulation during overvoltages to 276 | Undervoltage Correction | 2% output voltage regulation during undervoltages to 156 |
|
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display | Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual) | Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions | Alarm Cancel Operation | Alarm cancel switch | Audible Alarm | Unique audible alarms for all major UPS, environmental and power conditions (see manual) | LED Indicators | 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
|
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Response Time | Instantaneous | EMI / RFI AC Noise Suppression | Yes |
|
PHYSICAL |
Included Mounting Accessory Description | 2 sets of adjustable 4 post rack rails included (for UPS and battery pack components); 2-9USTAND tower kit included (supports up to 9U in tower format) | Installation Form Factors Supported with Optional Accessories | 2 post rackmount(2POSTRMKITHD) | Optional Mounting Accessory Notes | 2 sets of 2POSTRMKITWM required for 2 post rackmount installation of separate power module and battery pack | Primary Form Factor | Rackmount | UPS Power Module Dimensions (hwd, cm) | 13.3 x 44.4 x 66 | Rack Height (U Spaces) | 6 | Maximum Device Depth (cm) | 66 | UPS Power Module Weight (kg) | 19.9 | UPS Dimensions Details | Includes 3U power module and 3U battery pack | Included Battery Pack Dimensions (hwd / cm) | 13.3 x 44.4 x 63.5 | Included Battery Pack Weight (kg) | 62 | UPS Shipping Dimensions (hwd / cm) | 62.2 x 61 x 88.9 | Shipping Weight (kg) | 146.6 | Cooling Method | Fan | UPS Housing Material | Steel |
|
ENVIRONMENTAL |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius. | Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius. | Relative Humidity | 0 to 95%, non-condensing | AC Mode BTU / Hr. (Full Load) | 1412.3 | AC Economy Mode BTU / Hr. (Full Load) | 911.5 | AC Mode Efficiency Rating (100% Load) | 91% | AC Economy Mode Efficiency Rating (100% Load) | 94% | Audible Noise | 60 dBA at front side 1 meter | Operating Elevation (m) | 0 – 3000 m |
|
COMMUNICATIONS |
Communications Interface | DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface | Network Monitoring Port Description | RS232 and contact closure communications are located on two separate DB9 ports | PowerAlert Software | Included | Communications Cable | DB9 cable included |
|
LINE / BATTERY TRANSFER |
Transfer Time | No transfer time (0 ms.) in online, double-conversion mode | Transfer Time (Economy Mode) | Less than 1ms typical power failure response in optional economy mode | Low Voltage Transfer to Battery Power (Setpoint) | 156 | High Voltage Transfer to Battery Power (Setpoint) | 276 |
|
SPECIAL FEATURES |
Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | High Availability UPS Features | Automatic inverter bypass; Hot swappable batteries | Green Energy-Saving Features | High efficiency economy mode operation; Schedulable daily hours of economy mode operation |
|
CERTIFICATIONS |
UPS Certifications | Tested to UL1778 (USA). Also tested to CSA (Canada). More than this tested to NOM (Mexico). In addition to this provide CE. Also tested to GOST (Russia). Also tested to SASO (Saudi Arabia). Beyond this tested to IRAM (Argentina). More than this meets FCC Part 15 Category A (EMI). In addition to this provides the ROHS (Restriction of Hazardous Substances). |
|
WARRANTY |
Product Warranty Period (Worldwide) | 2-year limited warranty | Connected Equipment Insurance (U.S., Canada & Puerto Rico) | $250,000 Ultimate Lifetime Insurance |
|